| Customization: | Available |
|---|---|
| Breaking Capacity: | Low Voltage Circuit Breakers |
| Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency

| Technical data | YC7VA | YC7V | YC7A |
| Rated Working Voltage | AC 220V | ||
| Operation voltage range | AC 80V-300V | AC 80V-300V | |
| Rated frequency | 50Hz/60Hz | ||
| Overvoltage(>U)setting range | 130-300V | ||
| Undervoltage(<U)setting range | 80-210V | ||
| Rated current | 40/63A(subject to prodect label) | 1~40/63A(subject to prodect label) | |
| > U and <U trip delay | 1-999S | Default 30S | 0.5S(>Atrip delay) |
| Reset/start delay | 1-999S | Default 5S | 1~999S |
| Voltage measurement accuracy | 2% (Not exceeding 2% of the overall range) | 1% (Not exceeding 1% of the overall range) | |
| Rated insulation voltage | 400V | ||
| Output contact | 1NO | ||
| Electrical Life | 105 | ||
| Mechanical Life | 106 | ||
| Protection degree | IP20 | ||
| Pollution degree | 3 | ||
| Altitude | ≤ 2000m | ||
| Operating temperature | -50°C~55°C | ||
| Humidity | ≤50% at 40%(without condensation) | ||
| Storage temperature | -30°C~70°C | ||
| Current specification | 15A | 25A | 32A | 50A | 63A |
| Rated operating current(In, A) | 15 | 25 | 32 | 50 | 63 |
| Maximum operating current Imax(A, within 10min) | 25 | 30 | 40 | 60 | 80 |
| Max. power of load(kW) | 3.6 | 5.5 | 7 | 11 | 13.9 |
| NO. | Option code | Option | max | min | Default | Step | Unit | Description |
| P1 | Pt | Power-on delay | 999 | 1 | 5 | 1/10 | S | |
| P2 | rt | Recoverydelay | 999 | 1 | 30 | 1/10 | S | |
| P3 | oU | Overvoltage | 300 | 130 | 270 | 1/10 | V | Close overvoltage if greater than 300 |
| P4 | oUr | Overvoltage recovery value | 295 | 125 | 265 | 1/10 | V | Skip this setting when overvoltage is turned off |
| P5 | uU | Undervoltage | 210 | 80 | 170 | 1/10 | V | Close undervoltage if below 80 |
| P6 | uUr | Undervoltage recoveryvalue | 215 | 85 | 175 | 1/10 | V | Skip this setting when undervoltage is turned off |
| P7 | Utt | Overvoltage action delay | 10.0 | 0.1 | 0.5 | 0.1/1.0 | S | |
| P8 | UAd | Voltage correction | +10% | -10% | 0 | 0.5% | V | Long press settingis not recommended |
| P9 | oC | Overcurrent | 63.0 | 1.0 | 63.0 | 0.1/1.0 | A | Close overcurrent if greater than 63.0 |
| P10 | Ctt | Overflow as delay | 10.0 | 0.1 | 1.0 | 0.1/1.0 | S | |
| P11 | CC | Continuous overcurrent counting | 20 | 0 | 0 | 1 | Times | 0: Turn off counting |
| P12 | CAd | Current correction | +10% | -10% | 0 | 0.5% | A | Long press settingisnot recommended |
| P13 | FAd | Frequency correction | +2.5% | -2.5% | 0 | 0.1% | Hz | Modifying this value will affect the accuracy ofthe timer |
| P14 | FPd | Rapid power failure protection | on | off | on | MS | ||
P15 |
dS |
Display mode |
3 |
1 |
1 |
1 |
1:Standards | |
| 2: Manualswitch | ||||||||
| 3:Automatic switch | ||||||||
| P16 | Ar | Automatic reset | on | off | on | on: Self-recovery | ||
| off: Manual recovery | ||||||||
| P17 | Act | Action/knife mode | on | off | on | on: Protector working properly | ||
| off: knife mode | ||||||||
| P18 | EC | Energy saving mode | on | off | off | on: Open | ||
| off: Close | ||||||||
| P19 | Loc | Setup lock password | 999 | 000 | 112 | 1/10 | When this value is not 112, you can only view the parameter and cannot set it |