| Type | YCM1-63 | YCM1-125 | YCM1-160 | YCM1-250 | YCM1-400 | YCM1-630 | YCM1-800 | YCM1-1250 | YCM1-1600 | ||||||||
| Poles | P | 3 | 34 | 234 | 3P | 234 | 3 | 4 | 3 | 4 | 34 | 3 | 3 | ||||
| Rated current In | A | 10,16, 20,25, 32,40, 50,63 |
10,16, 20,25, 32,40, 50,63 80,100, 125 |
100, 125,140, 160 |
100,125, 140160, 180,200 225,250 |
225, 250, 315,350, 400 |
400,500, 630 |
630,700, 800 |
800,1000 1250 |
1600 |
|||||||
| Rated insulation voltage Ui |
V | 500 | 800 | ||||||||||||||
| Rated impu lse withstand voltage Uimp |
V | 6000 | 8000 | ||||||||||||||
| Rated operation voltage Ue |
V | AC400 | AC400/690 | ||||||||||||||
| Breaking capacity class | L | M | L | M | L | L | M | L | M | L | M | M | M | M | |||
| Limit short-circuit breaking capacity lcu |
kA | 400V | 25 | 50 | 35 | 50 | 35 | 35 | 50 | 50 | 65 | 50 | 65 | 75 | 85 | 85 | |
| 690V | 8 | 10 | 8 | 8 | 10 | 10 | 20 | 10 | 20 | 30 | 30 | 30 | |||||
| Working short-circuit breaking capacity Ics |
kA | 400V | 18 | 25 | 22 | 25 | 22 | 22 | 25 | 35 | 42 | 35 | 42 | 50 | 50 | 50 | |
| 690V | 4 | 5 | 4 | 4 | 5 | 5 | 10 | 5 | 10 | 15 | 15 | 15 | |||||
| Arcing distance mm | 50 | 100 | |||||||||||||||
| Operating frequency |
Electrical life | 1500 | 1500 | 1500 | 1000 | 1000 | 1000 | 500 | 500 | 500 | |||||||
| mechanical life | 8500 | 8500 | 8500 | 7000 | 4000 | 4000 | 2500 | 2500 | 2500 | ||||||||