Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General
YCB8s-63PV photovoltaic dedicated DC circuit breaker is mainly used in solar photovoltaic power generation systems.
The maximum working voltage can reach DC1200V, and the rated current is up to 63A.
It is used for overload and short circuit protection of the line, and can quickly cut off the fault current of the DC distribution system, protecting the important components in the solar power generation system - photovoltaic modules from the harm of DC side reverse current and AC side feedback current caused by inverter faults, ensuring the reliable operation of the solar photovoltaic power generation system.
Standards:IEC60947-2
Features
The product can achieve non-polar wiring, ensuring reliable equipment safety.
Product name | Shell frame | Breaking capacity | PV DC | Number of poles | Rated current | Operating voltage | |
YCB8s | - | 63 | H | PVn | 2P | 20A | DC600 |
YCB8s |
63 |
Default:6KA H:10KA |
PVn:Photovoltaic DC non-polarity |
1P 2P 3P 4P |
1A 2A 3A 4A 6A 10A 16A 20A 25A 32A 40A 50A 63A |
DC300 DC600 DC900 DC1200 |
Appearance diagram |
||||
Number of poles | 1P | 2P | 3P | 4P |
Rated operating voltage Ue (V) | DC300 | DC600 | DC900 | DC1200 |
Rated insulation voltage Ui (V) | DC300 | DC600 | DC900 | DC1200 |
Rated impulse withstand voltage Uimp (KV) | 6 | |||
Rated frame current (A) | 63 | |||
Rated current In (A) | 1,2,3,4,6,10,16,20,25,32,40,50,63 | |||
Ultimate short-circuit breaking capacity Icu (KA) | Default: 6; H:10 | |||
Instantaneous tripping characteristic | B,C,K | |||
Service life (times) | Mechanical 20000, electrical life 1500 | |||
Protection degree | IP20 | |||
Environmental temperature for use | -25°C~+40°C | |||
Altitude | ≤ 2000m | |||
Wiring ability(mm²) | 25 | |||
Connection | both upper and lower incoming lines are acceptable | |||
Use Category | A | |||
Standard | IEC60947-2 |
Rated current(A) | Overload tripping characteristics | Instantaneous tripping characteristics(A) | |
1.05In agreed non tripping time H (cold state) | 1.30In agreed tripping time H (hot state) | ||
In ≤ 63 | 1 | 1 | B(4In±20%) C(8In±20%) K(10In±20%) |
In > 63 | 2 | 2 |
Rated current(A) | Ambient temperature corresponding to rated current (A) | |||||||||||
In(A) | -25°C | -20°C | -10°C | 0°C | 10°C | 20°C | 30°C | 35°C | 40°C | 50°C | 60°C | 75°C |
6A | 10.12 | 9.77 | 9.03 | 8.26 | 7.49 | 6.75 | 6 | 5.59 | 5.19 | 4.75 | 4.62 | / |
10A | 17.41 | 16.75 | 15.41 | 14.04 | 12.71 | 11.35 | 10 | 9.09 | 8.21 | 7.9 | 8.7 | 7.86 |
16A | 21.72 | 21.15 | 20.15 | 19.12 | 18.08 | 17.04 | 16 | 15.49 | 15.1 | 14.38 | 13.52 | 12.75 |
20A | 25.86 | 25.79 | 24.61 | 23.47 | 22.32 | 21.16 | 20 | 19.43 | 18.83 | 18.58 | 17.1 | 16.3 |
25A | 32.41 | 31.74 | 30.37 | 28.98 | 27.69 | 26.35 | 25 | 24.33 | 23.65 | 23.3 | 24.7 | 23.8 |
32A | 44.83 | 43.62 | 41.29 | 38.96 | 36.67 | 34.33 | 32 | 30.83 | 29.67 | 30.7 | 30.8 | 30 |
40A | 50.34 | 49.35 | 47.51 | 45.62 | 43.73 | 41.87 | 40 | 39.04 | 38.11 | 38.6 | 36.2 | 35.8 |
50A | 63.79 | 62.48 | 59.99 | 57.48 | 54.98 | 52.5 | 50 | 48.76 | 47.48 | 47.1 | 47.5 | 46 |
63A | 80 | 78.46 | 75.38 | 72.28 | 69.17 | 66.09 | 63 | 61.46 | 59.93 | 55.6 | 53.8 | 52.4 |
Model |
YCB8s-63 OF | YCB8s-63 SD | YCB8s-63 MX | ||||
Appearance |
|||||||
Types |
1 2 14 |
94 |
2 |
C2 C1 |
|||
Number of contacts | 1NO+1NC | 1NO+1NC | / | ||||
Control voltage (VAC) |
110-415 48 12-24 |
||||||
Control voltage(V DC) |
110-415 48 12-24 |
||||||
Working current of contact |
AC-12 Ue/Ie: AC415/3A DC-12 Ue/Ie: DC125/2A |
/ |
|||||
Shunt control voltage |
Ue/Ie: AC:220-415/ 0.5A AC/DC:24-48/3 |
||||||
Width(mm) | 9 | 9 | 18 | ||||
Applicable Environmental Conditions and Installation | |||||||
Storage temperature(°C) | -40°C~+70°C | ||||||
Storage humidity | the relative humidity does not exceed 95% when at +25°C | ||||||
Protection degree | Level 2 | ||||||
Protection degree | IP20 | ||||||
Installation environment | Places without significant vibration and impact | ||||||
Installation category | Category II , Category III | ||||||
Installation method | TH35-7.5/DIN35 rail installation | ||||||
Maximum wiring capacity | 2.5mm² |