Customization: | Available |
---|---|
Application: | Industrial |
Speed: | Low Speed |
Still deciding? Get samples of US$ 10/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Multiple of setting current | Acting time | Initial state | Ambient air temperature |
1 | 1.0In | ≤2h non-tripping | Cold state | +40ºC±2ºC |
2 | 1.2In | ≤2h tripping | Start after 1 | +40ºC±2ºC |
The adjusting range of commuting current |
The cutting capacity for rated limit short circuit lcu,the cutting capacity for rated work short circuit lcs | |||||||
230/240V | 415V | 500V | 660V | |||||
Icu(kA) | Ics, %Icu(kA) | Icu(kA) | Ics, %Icu(kA) | Icu(kA) | Ics, %Icu(kA) | Icu(kA) | Ics, %Icu(kA) |
0.1-0.16 | 100 | 100 | 100 | 100 | 100 | 100 | -- | -- |
0.16-0.25 | 100 | 100 | 100 | 100 | 100 | 100 | -- | -- |
0.25-0.4 | 100 | 100 | 100 | 100 | 100 | 100 | -- | -- |
0.4-0.63 | 100 | 100 | 100 | 100 | 100 | 100 | -- | -- |
0.63-1 | 100 | 100 | 100 | 100 | 100 | 100 | -- | -- |
1-1.6 | 100 | 100 | 100 | 100 | 100 | 100 | -- | -- |
1.6-2.5 | 100 | 100 | 100 | 100 | 100 | 100 | 3 | 75 |
2.5-4 | 100 | 100 | 100 | 100 | 100 | 100 | 3 | 75 |
4-6.3 | 100 | 100 | 100 | 100 | 50 | 100 | 3 | 75 |
6-10 | 100 | 100 | 100 | 100 | 10 | 100 | 3 | 75 |
9-14 | 100 | 100 | 15 | 50 | 6 | 75 | 3 | 75 |
13-18 | 100 | 100 | 15 | 50 | 6 | 75 | 3 | 75 |
17-23 | 50 | 50 | 15 | 50 | 4 | 75 | 3 | 75 |
20-25 | 50 | 50 | 15 | 50 | 4 | 75 | 3 | 75 |
24-32 | 50 | 50 | 10 | 50 | 4 | 75 | 3 | 75 |
6-10 | / | / | 100 | 50 | 8 | 100 | 4 | 100 |
10-16 | / | / | 100 | 50 | 8 | 100 | 4 | 100 |
14-20 | / | / | 100 | 50 | 8 | 100 | 4 | 100 |
16-25 | / | / | 100 | 50 | 8 | 100 | 4 | 100 |
25-40 | / | / | 35 | 50 | 8 | 75 | 4 | 75 |
40-63 | / | / | 35 | 50 | 8 | 75 | 4 | 75 |
56-80 | / | / | 15 | 50 | 4 | 100 | 2 | 100 |
Series No. | Multip le of setting current | Initial status | Time | Expected results | Ambient temperature |
|
1 | 1.05 | Cold status | t≥2h | Non-tripping | +20°C±2°C | |
2 | 1.20 | Heat status (right after test.1) |
t<2h | Tripping | +20°C±2°C | |
3 | 1.50 | Heat status (right after test.1) |
Tripping class | 10A t<2min 10 t<4min |
Tripping | +20°C±2°C |
4 | 7.20 | Cold status | Tripping class | 10A 2s<t≤10s 10 4s<t≤10s | Tripping | +20°C±2°C |
Series No. | Multiple of setting current | Initial status | Time | Expected results | Ambient temperature |
||
Any 2 phase | The other | phase | |||||
1 | 1.0 | 0.9 | Cold status | t≥2h | Non-tripping | +20°C±2°C | |
2 | 1.15 | 0 | Heat status (right after test.1) |
t<2h | Tripping | +20°C±2°C |
Type |
Standard power ratings of 3-phase molors 50/60Hz in category AC-3 | Current setting range |
|||||
220V | 380V | 415V | 440V | 500V | 660V | ||
kW | kW | kW | kW | kW | kW | ||
YCP5-25-ME01 | - | - | - | - | - | - | 0.1-0.16 |
YCP5-25-ME02 | - | - | - | - | - | - | 0.16-0.25 |
YCP5-25-ME03 | - | - | - | - | - | - | 0.25-0.4 |
YCP5-25-ME04 | - | - | - | - | - | 0.37 | 0.4-0.63 |
YCP5-25-ME05 | - | - | - | 0.37 | 0.37 | 0.55 | 0.63-1 |
YCP5-25-ME06 | - | 0.37 | - | 0.55 | 0.75 | 1.1 | 1-1.6 |
YCP5-25-ME07 | 0.37 | 0.75 | 0.75 | 1.1 | 1.1 | 1.5 | 1.6-2.5 |
YCP5-25-ME08 | 0.75 | 1.5 | 1.5 | 1.5 | 2.2 | 3 | 2.5-4 |
YCP5-25-ME10 | 1.1 | 2.2 | 2.2 | 3 | 3.7 | 4 | 4-6.3 |
YCP5-25-ME14 | 2.2 | 4 | 4 | 4 | 5.5 | 7.5 | 6-10 |
YCP5-25-ME16 | 3 | 5.5 | 5.5 | 7.5 | 7.5 | 9 | 9-14 |
YCP5-25-ME20 | 4 | 7.5 | 9 | 9 | 9 | 11 | 13-18 |
YCP5-25-ME21 | 5.5 | 11 | 11 | 11 | 11 | 15 | 17-23 |
YCP5-25-ME22 | 5.5 | 11 | 11 | 11 | 15 | 18.5 | 20-25 |
YCP5-25-ME32 | 7.5 | 15 | 15 | 15 | 18.5 | 26 | 24-32 |
YCP5-80-ME10 | 1.1 | 2.2 | 2.2 | 3 | 3.7 | 4 | 6-10 |
YCP5-80-ME16 | 2.2 | 4 | 4 | 4 | 5.5 | 7.5 | 10-16 |
YCP5-80-ME20 | 4 | 7.5 | 7.5 | 7.5 | 10 | 11 | 14-20 |
YCP5-80-ME25 | 5.5 | 11 | 11 | 11 | 15 | 18.5 | 16-25 |
YCP5-80-ME40 | 11 | 18.5 | 22 | 22 | 25 | 33 | 25-40 |
YCP5-80-ME63 | 15 | 30 | 33 | 33 | 40 | 55 | 40-63 |
YCP5-80-ME80 | 22 | 40 | 45 | 45 | 55 | 63 | 56-80 |