Breaking Capacity: | Low Voltage Circuit Breakers |
---|---|
Operation: | Electric Type |
Speed: | Normal Type Circuit Breaker |
Arc-extinguishing Medium: | Air |
Installation: | Fixed |
Structure: | RCBO |
Samples: |
YCB6HLE-63 1P+N C25 10mA
|
---|
Customization: |
---|
Suppliers with verified business licenses
YCB6HLE-63 Series 1P+N 2P 3P 3P+N 4P RCBO 32A 63A Residual Current Breaker Overload Circuit Breakers
General
1.Protection against overload and short-circuit currents
2.Protection against the effects of sinusoidal alternating earth fault currents
3.Protection against indirect contacts and additional protection against direct contacts
4.Protection against fire hazard caused by insulation faults
5.Used in residential building
6.According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln,type D(10-20)ln
Type | Standard | IEC/EN61009-1 | |
Electrical | Poles | P | 1P+N,2,3,3P+N,4 |
features | Type(waveformoftheearthleakagesensed) | AC | |
Thermo-magneticreleasecharacteristic | B,C,D | ||
RatedcurrentIn | A | 6,10,16,20,25,32,40,50,63 | |
RatedvoltageUe | V | 230VAC(1P+N,2P)400VAC(3P,3P+N,4P) | |
RatedsensitivitylΔn | A | 0.03,0.05,0.1,0.3 | |
Ratedresidualmakingand | A | 500(In≤40A)630(In>40A) | |
breakingcapacitylΔm | |||
Ratedshort-circuitcapacitylcn | A | 4500 | |
BreaktimeunderlΔn | s | ≤0.1 | |
Ratedfrequency | Hz | 50/60 | |
Ratedimpulsewithstandvoltage(1.2/50)Uimp | V | 4000 | |
Dielectrictestvoltageatind.Freq.for1min | kV | 2 | |
InsulationvoltageUi | V | 500 | |
Pollutiondegree | 2 |
Suppliers with verified business licenses