Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
CNC Ycb6hle-63 Series RCBO 4.5ka 1p+N AC 230V/400V Residual Current Circuit Breaker with Over Current Protection
Type Standard | IEC/EN 61009-1 | ||
Electrical features | Poles | P | 1P+N, 2, 3, 3P+N, 4 |
Type(wave form of the earth leakage sensed) | AC | ||
Thermo-magnetic release characteristic | B, C, D | ||
Rated current In | A | 6, 10, 16, 20, 25, 32, 40, 50, 63 | |
Rated voltage Ue | V | 230V AC(1P+N, 2P) 400V AC(3P, 3P+N, 4P) | |
Rated sensitivity lΔn | A | 0.03, 0.05, 0.1, 0.3 | |
Rated residual making and breaking capacity lΔm | A | 500(In≤40A) 630(In>40A) | |
Rated short-circuit capacity lcn | A | 4500 | |
Break time under lΔn | s | ≤0.1 | |
Rated frequency | Hz | 50/60 | |
Rated impulse withstand voltage(1.2/50)Uimp | V | 4000 | |
Dielectric test voltage at ind.Freq.for 1min | kV | 2 | |
Insulation voltage Ui | V | 500 | |
Pollution degree | 2 | ||
Mechanical features | Electrical life | t | 4000 |
Mechanical life | t | 10000 | |
Contact position indicator | Yes | ||
Protection degree | IP20 | ||
Ambient temperature(with daily average≤35ºC) | ºC | -5~+40 | |
Storage temperature | ºC | -25~+70 | |
Installation | Terminal connection type | Cable/Pin-type busbar | |
Terminal size top/bottom for cable | mm² | 25 | |
AWG | 18-3 | ||
Terminal size top/bottom for busbar | mm² | 25 | |
AWG | 18-3 | ||
Tightening torque | N*m | 2 | |
In-Ibs | 18 | ||
Mounting | On DIN rail EN60715(35mm)by means of fast clip device | ||
Connection | From top |