Type | Standard | IEC/EN 60947-2 | |
Electrical features |
Rated current In | A | 63,80,100,125A |
Poles | P | 1,234 | |
Rated woltage Ue | V | 230/400 | |
Insulation voltage Ui | V | 500 | |
Rated frequency | Hz | 50/60 | |
Rated breaking capacity | A | 6000 | |
Rated impulse withstand voltage(1.2/50) Uimp | V | 6000 | |
Dielectric test voltage at ind. Freq. for 1min | kV | 25 | |
Pollution degree | 3 | ||
Thermo-magnetic release characteristic | (C)li=8In,(D)li=12ln | ||
Mechanical features |
Electrical life | t | 1500 |
Mechanical life | t | 10000 | |
Contact position indicator | Yes | ||
Protection degree | P20 | ||
Reference temperature for setting of thermal element |
30 | ||
Ambient temperature (with daily average s35ºC) |
ºC | 5~+40(Spedal application please refer to temperature compensation cormection) |
|
Sto rage temperature | ºC | 25≈+70 | |
Installation | Terminal connection type | ºC | Cable/Pin-type busbar |
Terminal size top / bottom for cable | mm² | 50 | |
AWG | 18-1/0 | ||
Terminal size top / bottom for busbar | mm² | 50 | |
AWG | 18-1/0 | ||
Tightening torque | N*m | 3.5 | |
In-1bs | 31 | ||
Mounting | On DIN rail EN60715(35mm)by means of fast clip device | ||
Connection | From top and bottom |