Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 4.8/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General
1. Protection against overload and short-circuit currents
2. Protection against the effects of sinusoidal alternating earth fault currents
3. Protection against indirect contacts and additional protection against direct
contacts.
4. Protection against fire hazard caused by insulation faults
5. Used in residential building
6. According to the type of instantaneous release classified as follows: type B(3-5)ln, type C(5-10)ln
Release
Type | Test current | Tripping time | Expected result |
B,C | 1.13In | t≤1h(In≤63A) | Not tripping |
1.13In | t≤2h(In>63A) | ||
B,C | 1.45In | t<1h(In≤63A) | Tripping |
1.45In | t<2h(In>63A) | ||
B,C | 2.55In | 1s | Tripping |
2.55In | 1s32A) | ||
B | 3In | t≤0.1s | Not tripping |
C | 5In | t≤0.1s | |
B | 5In | t<0.1s | Tripping |
C | 10In | t<0.1s |
Type | Standard | lEC/EN 61009-1 | |
Electrical features |
Leakage type | Electromagnetic type | |
Rated current In | A | 6, 10, 16, 20, 25, 32, 40 | |
Type (wave form of the earth leakage sensed) | A, AC | ||
Poles | P | 1P+N | |
Rated voltage Ue | V | 230 | |
Insulation voltage Ui | V | 500 | |
Rated frequency | Hz | 50/60 | |
Rated breaking capacity Icn | A | 6000 | |
Rated impulse withstand voltage (1.2/50) Uimp | V | 4000 | |
Dielectric test voltage at ind. Freq. for 1min | kV | 2 | |
Rated sensitivity IΔn | A | 0.03, 0.05, 0.1 | |
Break time under IΔn | s | ≤0.1 | |
Rated residual making and breaking capacity IΔm | A | 500 | |
Pollution degree | 2 | ||
Mechanical features |
Electrical life | t | 4000 |
Mechanical life | t | 8000 | |
Protection degree | IP20 | ||
Storage temperature | ºC | -25~+70 | |
Ambient temperature (with daily average≤35ºC) | ºC | -5~+40 | |
Installation |
Terminal connection type | Cable/U-type bar/Pin-type busbar | |
Terminal size top / bottom for cable | mm² | 16 | |
AWG | 18-5 | ||
Terminal size top / bottom for busbar | mm² | 16 | |
AWG | 18-5 | ||
Tightening torque | N*m | 1.2 | |
In-Ibs | 11 | ||
Mounting | On DIN rail EN 60715(35mm)by means of fast clip device | ||
Connection | From top and bottom |