Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Manual Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Function
1. Personnel and fire protection
2. Cable and line protection against overload and short-circuits.
Selection
1. In ≤ 30 mA: additional protection in the case of direct contact.
2. In ≤300 mA: preventative fire protection in the case of ground fault currents.
3. AC class - Tripping is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase.
Release
Type | Tripping time | I△n(A) | Expected result | Note | |||||
I△n | 2I△n | 5I△n | 6I△n | ||||||
General | 63, 80, 100, 125 |
≥0.03 | 0.1 | 0.07 | 0.04 | 0.04 | Minimum time for tripping | ||
Time delay |
Time limit for not tripping |
0.06s | ≥0.03 | 0.3 | 0.2 | 0.15 | 0.15 | Minimum time for tripping | |
≥0.03 | 0.13 | 0.06 | 0.05 | 0.04 | Minimum time for not tripping | ||||
0.1s | ≥0.03 | 0.6 | 0.4 | 0.3 | 0.2 | Minimum time for tripping | |||
≥0.03 | 0.23 | 0.1 | 0.06 | 0.05 | Minimum time for not tripping |
Type | Test current | Tripping time | Expected result |
C,D | 1.05In | t≤1h(In≤63A),t≤2h(In≤63A) | Not tripping |
C,D | 1.3In | t≤1h(In≤63A),t≤2h(In≤63A) | Tripping |
C,D | 2.55In | 1s<t<120s | Tripping |
C | 8In ×80% | t≤0.2s | Not tripping |
D | 12In ×80% | t≤0.2s | Not tripping |
C | 8In × 120% | t<0.2s | Tripping |
D | 12In × 120% | t<0.2s | Tripping |
Type | Standard | IEC/EN 60947-2 | |
Electrical features Mechanical features |
Type (wave form of the earth leakage sensed) | AC | |
Thermo-magnetic release characteristic | (C)Ii=8In,(D)Ii=12In | ||
Rated current In | A | 63, 80, 100 | |
Poles | 1P+N, 2P, 3P, 3P+N, 4P | ||
Rated voltage Ue | V | 230/400 | |
Rated sensitivity IΔn | A | 0.03, 0.1, 0.3 | |
Rated short-circuit capacity lcn | A | 6000 | |
Break time under I△n | s | ≤0.1 | |
Rated impulse withstand voltage (1.2/50)Uimp |
V | 4000 | |
Dielectric TEST voltage at ind. Freq. for 1min | kV | 1.89 | |
Insulation voltage Ui | V | 500 | |
Pollution degree | 3 | ||
Electrical life | 1500 | ||
Mechanical life | 8500 | ||
Contact position indicator | Yes | ||
Protection degree | IP20 | ||
Ambient temperature(with daily average≤35ºC) | ºC | -5... +40 | |
Storage temperature | ºC | -25... +70 | |
Installation |
Terminal connection type | Cable/Pin-type busbar | |
Terminal size top/bottom for cable | mm² | 16~50 | |
AWG | 6-1/0 | ||
Terminal size top/bottom for busbar | mm² | 16~35 | |
AWG | 6-2 | ||
Tightening torque | N·m | 3.5 | |
In-Ibs. | 31 | ||
Mounting Connection | On DIN rail EN 60715 (35mm) by means of fast clip device From top |