Our Services
Product Description
General
Integrated circuit breaker is one of the new circuit breakers developed by advanced technol- ogy, the product is suitable for general distribution system, new energy distribution system, multi-energy distribution network, inverter and distributed power rotary motor power supply grid-connected operation and protection and other occasions, it has isolation function and small size, high breaking capacity, and other multi-functional characteristics.
Standards: IEC60947-1 ,IEC60947-2
Operating Conditions
The ambient air temperature is -5 °C ~ +40 °C(beyond the range can be reduced capacity use), and the average value of 24h does not exceed +35°C ;
The elevation of the installation site does not exceed 2000m, more than 2000m capacity reduction use;
The relative humidity of the air at the installation site does not exceed 50% when the maxi- mum temperature is +40°C , and can have a higher relative humidity at lower temperatures, such as 90% at 20°C .Special measures should be taken for condensation occasionally
caused by temperature changes;
Pollution level is level 3;
Circuit breaker main circuit installation category IV, the rest of the auxiliary circuit and control circuit installation category III;
The circuit breaker should be installed in a place where there is no explosion risk, no con- ductive dust,no rain and snow attack, and no enough to corrode metal and destroy insula- tion.
Technical data
Type |
|
YCW9X-1600 |
Bracket rating Current Inm(A) |
|
1600 |
Rated current In(A) |
200,400,6 |
30,800,1000,1250,1600 |
Rated operating voltage Ue(V) |
A |
C400V,AC800V |
Rated insulation voltage Ui(V) |
|
1000 |
Rated impulse withstand voltage Uimp(kV) |
|
12 |
Power frequency withstand voltage U(V)1min |
|
3500 |
Number of poles |
|
3,4 |
N-pole rated current In(A) |
|
100%In |
Rated limit short-circuit breaking capacity Icu(kA)(valid value) |
AC400V |
|
60 |
AC800V |
|
32 |
Rated operating short-circuit breaking capacity Ics(kA)(valid value) |
AC400V |
|
50 |
AC800V |
|
20 |
Rated short-circuit ability Icm(kA) (Peak) |
AC400V |
|
143 |
AC800V |
|
105 |
Rated short-time withstand current Icw(kA)/1s(valid value) |
AC400V |
|
50 |
AC800V |
|
20 |
Total breaking time (no additional delay)(ms) |
|
25 |
Closing time(ms) |
|
Max70 |
Electrical life (s) |
AC400V |
|
maintenance-free 1500 |
maintenance-free 4500 |
AC800V |
|
maintenance-free 1200 |
Be maintained 3500 |
Mechanical life (second) |
Maintenance-free |
|
4500 |
Be maintained |
|
8500 |
Overload long delayprotection
The overload and long delay protection function generally protects the cable from overload.
Overload long delay protection parameter setting
Overload protection parameter setting table
Parameter name |
Adjustment range |
Remark |
Action current set value Ir |
=(0.2 ~ 1.0)In+OFF,Adjust the step =1A. |
|
Protection curve type |
Curve 1: Standard inverse time Curve 2: Fast inverse time
Curve 5: High voltage fuse compatibility Curve 6: Universal inverse time (I²t) |
For distribution protection, the upper limit of Ir is 1.0In. For generator protection, the upper limit of Ir is 1.25In. "OFF" indicates that the function is out. |
Delay time set Tr |
C01~C16 |
Cooling time setting |
Instantaneous,10min,20min,30min,45min,1h,2h |
Parameter name |
Adjustment range |
Remark |
Action current set value Ir |
=(0.2 ~ 1.0)In+OFF,Adjust the step =1A. |
|
Protection curve type |
Curve 1: Standard inverse time Curve 2: Fast inverse time
Curve 5: High voltage fuse compatibility Curve 6: Universal inverse time (I²t) |
For distribution protection, the upper limit of Ir is 1.0In. For generator protection, the upper limit of Ir is 1.25In. "OFF" indicates that the function is out. |
Delay time set Tr |
C01~C16 |
Cooling time setting |
Instantaneous,10min,20min,30min,45min,1h,2h |
Peculiarity |
Current multiple(n=I/Ir) |
Action characteristic |
Delay error |
Inactive characteristic |
n ≤ 1.05 |
>2h No action |
|
Action characteristic |
n>1.2 |
< 1h action |
|
Delay characteristic |
n>1.2 |
Characteristic curve, factory default characteristic curve 3 EI(G) |
±10% |
peculiarity |
Current multiple(n=I/Ir) |
Action characteristic |
Delay error |
Inactive characteristic |
n ≤ 0.95 |
>2h No action |
|
Action characteristic |
n>1.05 |
< 1h action |
|
Action delay |
n>1.05 |
Characteristic curve 6, generator protection characteristic curve: t=tr•(1n.2)2 |
±10% |
The controller provides 6 overload protection characteristic curves, which are expressed as follows:
Curve 1. Standard inverse time (SI):
Curve 2, Fast inverse time (VI):
Curve 3, Express inverse time (general purpose)EI(G):
Curve 4, Express inverse time (motor use)EI(M):
Curve 5, High Voltage fuse Compatibility (HV):
Curve 6, universal inverse time (I²t):
In the above 6 formulas: t: inverse time delay action time (seconds, s)
K: curve rate;
n: The multiple of the actual fault current relative to the long delay protection setting, that is,
tr: The delay time when n is equal to some eigenvalue (seconds, s)
Protection function
Thermal memory function
In order to prevent repeated or periodic overload, the controller tracks andrecords the thermal effect of the load current. When the thermal effect of theoverload accumulates to a predetermined level, the trip will be caused. The waythe heat capacity changes is determined by the curve
chosen.
The heat capacity increases when the measured current value is greater than1.1Ir. When the circuit breaker returns from overload state to
non-overload stateafter tripping due to overload long delay fault or inverse time short circuit fault,the heat capacity decreases exponentially. Us- ers can set the heat capacitycooling time: instantaneous, 10 minutes, 20 minutes, 30 minutes, 45 minutes, 1hour, 2 hours. When the controller does not use the auxiliary power supply, theheat capacity is cleared to zero after the circuit breaker is broken, and the heatcapacity accumula- tion is shown in Figure 2(A).
When the controller uses auxiliary power supply, the heat capacity decreasesaccording to the heat dissipation law after the breaker is broken, and the heatcapacity continues to change according to the current at this time on the basisof the original after re-closing. The change of heat capacity is shown in Figure 2(B).
Short circuit delay protection
Short circuit delay protection is set for Class B circuit breaker to achieve selectiveprotection, for medium strength short circuit fault. Users can choose either fixedtime mode or inverse time mode according to their needs.
3H type controller short delay protection can be optional area interlock function,when the short circuit fault occurs in the circuit breaker outlet
side, short circuitdelay will jump the circuit breaker instantaneously; When the short-circuit faultoccurs on the outgoing side of the next level cir- cuit breaker, the short-circuitdelay is tripped after the agreed delay time. The implementation of this functionneeds to be combined with the use of programmable IO ports (DI and DO),DI is used to detect the area interlock signal of the next level circuit breaker, and DO is used to send the interlock signal of the upper level circuit breaker.
Short circuit delay protection parameter
Setting current: Isd |
Isd=1.25~15IR+OFF,OFF Indicates that the short delay protection is disabled |
Constant time-lag Inverse time lag |
Setting time tsdSetting time tsd |
tsd=d0.1s~d1.0s+OFF, A d before the time indicates a definite time limit |
Action time (s) |
T=tsd |
Setting time tsd |
tsd=0.1s~1.0s+OFF,OFF Indicates alarm only without tripping |
Inverse time lag |
Action characteristic |
Actions between 0.9 and 1.1 Isd |
≤ 0.9: No action |
T=max{Tsd ,( )2× Tsd} |
>1.1: Delay action |
precision |
Accuracy ±10% (inherent error ±40ms) |
Thermal memory function |
15min+OFF (Factory default OFF, only valid for inverse time limit) |
Note:IR=oFF when ,Isd=1.25~15In+OFF;
Type 2, type 3 short delay inverse time delay characteristic curve 1~6, with overload long delay, but the curve speed is 10 times faster;
Use tips
1. type 2 and type 3 short delay inverse time delay characteristics are the same as overload long delay delay characteristics, only the action delay time is 1/10 of the long delay.
2. When the fault occurs, the protection is in a cold state (that is, the heat capacity =0), whether it is a long delay action or a short delay action, the action delay time is not less than the short delay time set value. In this case, the delay characteristic of short delay protection Is related to the Isd and IS setting values:
1) When Isd<1s or 1s=OFF, the controller only has a time-limit function; See Figure 3(A).
2) When Isd>1s, the controller has both inverse time limit and fixed time limit protection functions; See Figure 3(B).
3) When Is ≠ OFF,Isd=OFF, the controller only has the inverse Time protection function, then the inverse time characteristic curve is called IDMT(InverseDefinite Minimum Time) inverse time characteristic. See Figure
3(C). For IDMT inverse time feature, refer to GB14048.1-2006 for the note 2.4.27. 4) When Isd=Is=OFF, the short delay protection function is disabled.
3. When the fault occurs, the protection is in a hot state (that is, the heat capacity ≠ 0), then the action delay time is not limited by the set value of the short delay time limit time.
Short circuit instantaneous protection
The instantaneous protection function is to prevent the solid short circuit of the distribution system, such faults are generally phase faults, short circuit current is relatively large, need to be quickly disconnected.
Characteristic parameters of short circuit instantaneous protectio
Setting current Ii(A) |
box I |
1.0In~50kA+OFF |
box |
=1.0In~75kA+OFF |
box |
=1.0In~100kA+OFF |
Action characteristic |
0.85~1.15Ii In-between action |
≤ 0.85 Inaction |
> 1.15 Instantaneous action (natural action time ≤ 50ms) |
Setting current Ii(A) |
box I |
1.0In~50kA+OFF |
box |
=1.0In~75kA+OFF |
box |
=1.0In~100kA+OFF |
Action characteristic |
0.85~1.15Ii In-between action |
≤ 0.85 Inaction |
> 1.15 Instantaneous action (natural action time ≤ 50ms) |
MCR and HSISC Protection
The on-off/off (MCR) and off-limit trip (HSISC) functions are instantaneous protection functions. MCR protection protects the switching ability of the circuit breaker to prevent the switch damage caused by exceeding the switching limit current when the circuit breaker is switched on. The
protection works in the moment of opening and closing of the circuit breaker (within 100ms). HSISC protection protects the limit carrying capaci- ty of the circuit breaker, prevents the switch from carrying more than the limit breaking current, and takes effect after closing 100ms.
MCR and HSISC Protection parameter setting table
Parameter name |
Parameter name |
Set the step size |
MCR Operation current set value |
30~100kA+OFF |
1kA |
HSISC Operation current set value |
30~100kA+OFF |
30~100kA+OFF 1kA |
Use tips
1. MCR and HSISC setting values are generally set when the circuit breaker is delivered, according to thebreaking capacity of the circuit break- er, and are not adjustable by the end user.
2. M-type controller factory default MCR=OFF,HSISC=OFF; H type factory default MCR=30kA,HSISC=50KA.
Protection function
Neutral line protection
Neutral line protection is designed to adapt to the increasingly complex distribution system and the increasing number of neutral line faults. It is suitable for 3P+N or 4P circuit breaker configurations. The controller provides five neutral line protection modes: 50%N, 100%N, 160%N, 200%N and 0FF. When the neutral line is thin, it can be protected by 50%N method; When the neutral line is the same as other phase lines, it can be
protected by 100%N. When the harmonics in the power grid are relatively serious, 160%N or 200%N can be used for protection. The neutral line protection characteristic is the same as the overload long delay action characteristic.
Neutral line protection parameter setting table
Protection mode |
Long delay |
Short time delay |
Instantaneous movement |
Ground connection |
Scope of application |
50%N |
Ir/2 |
Isd/2 |
Ii |
Ig |
Distribution system where the cross-sectional area of the neutral line is equal to 1/2 of the cross-sectional area of the phase line |
100%N |
Ir |
Isd |
Ii |
Ig |
Distribution system in which the crosssectional area of the neutral line is equal to the cross-sectional area of the phase line |
160%N |
1.6Ir |
1.6Isd |
Ii |
Ig |
Distribution system where the crosssectional area of the neutral line is 1.6 times that of the phase line |
200%N |
2Ir |
2Isd |
Ii |
Ig |
Distribution system where the crosssectional area of the neutral line is twice the cross-sectional area of the phase line |
OFF |
/ |
/ |
/ |
/ |
The neutral protection function is disabled |
Use tips
1. The 1/2N mode is used as an example to illustrate the actual situation of neutral line protection: If a circuit breaker sets Ir=2000A,Is-
d=8000A,Ii=24000A,Ig=600A, the neutral line Ir=1000A,1sd=4000A,li=24000A,Ig=600A. When the current of the neutral line is greater than 1200A(1.2Ir), the neutral line long delay protection is enabled.
2. The fundamental (50Hz) currents in the neutral line of the three-phase load balancing circuit cancel each other, but 3, 9, 15... Odd times of equal order third harmonic currents are not cancelled but superimposed, which is why neutral lines are often overloaded (1). Therefore, the neutral line protection plays an effective role in protecting the cable heating aging caused by the 3n harmonics of the neutral line. IEC60364 Neutral line protection is required in this case.
3. The use of neutral line protection in 3P+N structure should pay attention to the design requirements of the distribution system. If the design requirements of the distribution system cannot break the neutral line but still have specific requirements for the neutral line overcurrent pro- tection, the protection function can be activated.
4. In the IEC60364 standard also stipulates that for TT, TN-S, IT systems, if the neutral line cross-sectional area is smaller than the phase line, neutral line overcurrent protection should be used; Neutral line protection should not be used in TN-C systems.
Earth fault protection
The IEC60364 grounding fault is defined as a short circuit fault between the phase line and the ground or grounded metal pipe structure or de- vice shell. Ground fault protection applies to the TN system, that is, the power distribution system where the neutral point of the power supply is grounded and the device enclosure is connected to the neutral line. The ground fault current can reach kA level strength.
It varies according to the specific details of the TN system and the circuit breaker configuration. There are three main modes of ground fault protection:
First, NFPA/EGFP mode;
Second, limited (REF)/ unrestricted (UEF) grounding protection; Third, standby ground protection (SEF).
Protection function
NFPA/EGFP Ground protection mode
1. This Protection mode is a protection policy developed by the National Fire Protection Association for TB systems in the NFPA70 standard, called Ground Fault Protection of Equipment (EFGP). It has the following points:
2. The neutral point of the distribution system must be directly Grounded (Solidly Grounded), and the grounding circuit cannot be strung into any resistance or reactance.
3. The maximum current setting value of the protection cannot exceed 1200A; When the fault current is greater than 1200A, neither the inverse time limit nor the fixed time limit delayshall exceed 1s.
4. There are two types of NFPA/EGFP ground fault protection:First, the vector sum mode (also known as residual current mode, type T), that
is, the ground fault current is equal to the vector sum of the phase line and neutral line current. Figure 4(A) and 4(B) show the vector sum mode of the ground current of 4P and 3P+N respectively.Second, the Ground current mode (W type), that is, an independent current trans- former detects the current of the Ground Return circuit of the power supply, and the current detected by other phase line transformers does not participate in the protection. As shown in Figure 4(C).
Use tips
1. The location of the ZCT configuration in the ground current mode is very important for the effectiveness of protection. It must be installed in the Ground Return circuit of the power supply (transformer). The ground return circuit refers to the neutral point of the transformer grounding wire, and the neutral line is the circuit between the point and the earth.
2. If the 3P circuit breaker is configured in a TN system and requires ground fault protection, it must be used in 3P+N mode (as shown in Fig- ure 4(B)) or ground current mode (as shown in Figure 4(C)). Otherwise, disable the grounding fault protection function to prevent the control- ler from misoperating.
3. In the case of FIG. 4(B) and 4(C), the maximum distance between the neutral line CT or ZCT and the circuit breaker is less than 10 meters. Interference caused by excessively long signal transmission may lead to misoperation.
NFPA Ground protection mode characteristic parameters
Setting current (Ig) |
In ≤ 1200A In>1200A |
Ig=(0.2~1)In+OFF; Ig=240~1200A+OFF; |
Step: 1A. OFF indicates that the function is disabled |
Action characteristic |
0.8~1.0Ig In-between action |
≤ 0.8 Ig Inaction |
≥ 1.0 Ig Delay action |
Setting time (tg) |
0.1~1.0s |
Action time |
Inverse time lag |
T=max{( )2Tg,Tg};n= ;Igm= { 1(I)0I0(n),In(1)212(0A)00A Error: ±15%(inherent ±40ms) |
Constant time-lag |
T=Tg; Rrror: ±40ms≤ 0.9: No action |
Ground area interlock(ZSI) |
The controller must be equipped with ZSI function to have this; One switch output (DO) is set to ZSI output; One switch input (DI) is set to ZSI input; |
Use tips
1. The factory default protection mode of the controller is NFPA. When current (Ig) is set to OFF, thefunction is turned off;
2. In order to facilitate switching between inverse time limit and fixed time limit mode, when setting Tg parameters, if 0.10~1.00 is displayed, it means that the current setting value is inverse time limit If the value d0.10 to d1.00 is displayed, the current value is a specified time limit.
3. For vector and form, transformer breakage will directly lead to serious deviation of current vector and sum, resulting in misoperation. There- fore, once the controller self-diagnosis function detects the fault of the transformer broken line, the protection mode will be automatically
shielded and the self-diagnosis alarm will be started.
Earth alarm The ground alarm function and the ground protection function of the Type 3 controller are independent of each other, and exist at the same time, with different setting parameters. Leakage protection Leakage protection is applicable to the leakage fault caused by insulation damage or the leakage fault caused by human contact with the con- ductive part of the leakage. The leakage current I △ n is directly expressed in amperes and has nothing to do with the rated current of the circuit breaker. The zerosequence sampling method is adopted, and a zero-sequence current transformer is required. This kind of transformer has high sampling accuracy, high sensitivity and is suitable for small current protection. Leakage protection characteristic parameters |
Setting current (A) |
I △ n |
0.5~30A+OFF(Level difference 0.1A,OFF indicates exit) |
Action characteristic |
in (0.8~1.0)I △ n In-between action |
≤ 0.8I △ ninaction |
>1.0I △ nDelay action |
Delay (s) |
Tg(s) |
0.06,0.08,0.17,0.25,0.33,0.42,0.5,0.58,0.67,0.75,0.83,instantaneous |
precision |
±10%(Inherent 40ms) |
Setting value of leakage protection delay time |
Setting time |
0.06 |
0.08 |
0.17 |
0.25 |
0.33 |
0.42 |
0.5 |
0.58 |
0.67 |
0.75 |
0.83 |
Instantaneous |
Multiple of fault current |
Max disconnect time (s) |
I △ n |
0.36 |
0.5 |
1 |
1.5 |
2 |
2.5 |
3 |
3.5 |
4 |
4.5 |
5 |
0.02 |
2I △ n |
0.18 |
0.25 |
0.5 |
0.75 |
1 |
1.25 |
1.5 |
1.75 |
2 |
2.25 |
2.5 |
0.02 |
5I △ n /10I △ n |
0.072 |
0.1 |
0.2 |
0.3 |
0.4 |
0.5 |
0.6 |
0.7 |
0.8 |
0.9 |
1.0 |
0.02 |
Leakage protection can also be divided into two sections, inverse time limit and fixed time limit; When I/ I △ n<5 is the inverse time limit, when I/ I △ n ≥ 5 is the fixed time limit; Leakage protection characteristic curve and protection conditions are as follows:
T={(6×TIg)/5 (I/I △ n) n ≥ 5)
For example, if the leakage delay time is set to Tg=0.06s, when I=I △ n,t=0.36s; When I=2I △ n,t=0.18s; When I ≥ 5I △ n,t=0.072s;
Load monitoring
Load monitoring can be used to forecast alarms and control branch loads. Action basis can be based on power or current action, there are
two modes of action: Mode 1: Two loads can be independently controlled. When the operating parameters exceed the setting value, the
corresponding load monitors the DO delay action (the corresponding DO function needs to be set), and controls the load splitting of two
branches to ensure power supply for the main system. Mode 2: Generally used to control the load of the same branch, when the operating
parameter exceeds the starting value, "load one" DO delay action (the action form can be pulse mode or level mode) to break the branch load; If the running parameter value is lower than the return value after breaking, and after the delay setting time, "load 1" DO return, "load 2" DO action (the action form can be pulse mode or level mode), switch on the broken load, and restore the system power supply.
Measuring function
Current measurement
The controller can measure three line currents (Ia, Ib, Ic), neutral line current (IN),ground current (Ig) or leakage current (I △ n) in realtime, suit- able for 50Hz/60Hz power grids. Measurement method: true RMS value or fundamental RMS value; Measuring range :Ia, Ib, Ic, IN not less than 25 times In(circuit breaker rated current). Measurement accuracy: within the range of 2In, the measurement error is ±1.5%; ±5% above 2In;
(Use tip) : When the measured value is less than the lower limit of the range, 0 is displayed.
Voltage measurement
Real-time measurement of line voltages (Uab, Ubc, Uca, UMAx) and phase voltages (Uan, Ubn, Ucn) for 50/60Hz power grids. Voltage mea- surement depends on the grid structure and circuit breaker configuration.
Measurement method: true effective value;
Measuring range :30V ~ 1200V(when the voltage is lower than the lower limit, it is displayed as 0V); Measurement accuracy :±1.5%.
Self-diagnostic information recording
The self-diagnosis function of the controller is mainly used for the inspection and maintenance of its own operating status. It can detect the
transformer broken line,magnetic flux broken line, circuit breaker rejection, contact maintenance, AD fault, XT clock fault, E2ROM fault and
other own faults in real time. When the self-diagnosis fault occurs, the current self-diagnosis fault information can be found in the"Current alarm" menu option A DO alarm signal can be sent, and the self-diagnostic information is recorded in the alarm record.
Self-diagnostic fault information table
Self-diagnosis fault display content |
Self-diagnostic fault description |
Troubleshooting method |
E-L1 E-L2 E-L3 E-LN |
Indicates that the current transformer L1, L2, L3, and Ln are disconnected |
Check whether L1, L2, L3, Ln wires of the secondary end of the current transformer are broken or broken, or whether the connection between L1, L2, L3, Ln and the circuit board is loose. |
E-CT E-11 |
The controller trip coil is disconnected |
Check whether the tripping magnetic flux and the circuit board are properly connected; |
E-JD E-12 |
The controller does not detect that the circuit breaker is successfully opened |
Check whether the small switch detection mechanismworks normally; |
E-13 |
Contact wear value >100% |
The main contact needs to be maintained. After the maintenance is complete, manually reset the contact Contact wear value is restored to 0 |
E-02 |
The system A/D sampling circuit is faulty. |
The controller cannot be used. Contact the manufacturer |
E-01 |
The external memory chip is faulty |
Power off and restart to see whether the fault disappears. If the fault still exists, it is required To replace the external E2ROM memory chip |
DO Feature
The controller has four sets of independent programmable I/O ports, which can be set according to the needs of the customer, and the internal relay contact output (contact capacity of 250VAC/5A,30VDC/5A). Relay definable functional states:
F and M controllers output DO parameter Settings |
Function setting |
Short circuit instantaneous fault trip |
Ground or leakage fault trip |
Ground or leakage fault trip |
Short circuit delay fault trip |
Overload long delay fault trip |
Fault trip |
Load monitoring 1 Unload the output |
Load monitoring 2 Unload output |
The system self-diagnoses faults |
Power grid fault state alarm |
Remote switching |
Remote closing |
Execution mode |
The fault trip switch signal, after the fault disappears, press the light clearing key to return |
Others are 100ms pulse signal output |
3H controller output DO parameter setting |
Function setting |
Be common |
Give an alarm |
Fault trip |
Self-diagnostic alarm |
Load I unloading |
Load II unloading |
N-phase fault |
Long delay trip |
Short delay trip |
Instantaneous trip |
MCR trip |
HSISC trip |
Ground trip |
Leakage trip |
The Iunbal trip |
A trip is required |
B trip is required |
A C trip is required |
N trip is required |
Undervoltage trip |
Overvoltage trip |
The Uunbal trips |
Underfrequency trip |
Overfrequency tripping |
Phase sequence trip |
Reverse power trip |
Overload warning |
Earth alarm |
Leakage alarm |
Iunbal call the |
Call the with "A" |
Call the "B" alarm |
Need to use C alarm |
Need N alarm |
Undervoltage alarm |
Overvoltage alarm |
Uunbal, call the |
Underfrequency alarm |
Overfrequency alarm |
Reverse power alarm |
Phase sequence alarm |
Communication failure |
ZS1 Output |
Remote switching |
Remote closing |
|
|
|
Execution mode |
Normally open level |
Normally closed level |
Normally open pulse |
Normally closed pulse |
DI Input function Area Selective Interlocking (ZSI)
Zone selective interlocking (ZSI) includes short circuit interlocking and ground interlocking, where two or more circuit breakers are connected as shown in Figure 15:
1. when the short circuit or ground fault occurs in the position of the lower circuit breaker (2# ~ #4circuit breaker) outlet side (such as position 2), the lower circuit breaker instantaneously trips, and sends a regional interlock trip signal to the upper circuit breaker (#1 circuit breaker); The upper circuit breaker receives the regional interlock trip signal and delays according to the parameters set by the short circuit or ground protection. If the fault current is cancelled during the delay of the upper circuit breaker, the protection returns and the upper circuit breaker does not operate. If the fault current does not cancel after the lower circuit breaker trips, the upper circuit breaker acts according to the set parameters of short circuit or ground protection to cut out the fault line.
2. When the short circuit or ground fault occurs between the upper circuit breaker (#1 circuit breaker) and the lower circuit breaker (2# ~ #4 cir- cuit breaker) (such as position ), the upper circuit breaker does not receive the regional interlock signal, and therefore the instantaneous trip, quickly cut the fault line.
Use tips
The ZSI function must be equipped with a set of DO(ZSI output in level mode) and a set of DI(ZSI input) as the electrical connection of the upper and lower circuit breakers; Please inform the manufacturer when ordering. Zone interlock is only available on 3H products.
Zonal selective interlocking (ZSI) is designed to reduce the fault stress that electrical distribution equipment suffers during short circuits or
ground faults. The ZSI system works with a pre-collaborative(coordination of operating parameters between distribution devices) distribution
system, which reduces the stress (damage) caused by faults by reducing fault clearance time, and maintains coordination between short-circuit or ground fault protection devices in the system.
Test function
The controller can simulate the instantaneous trip action for the trip test during field debugging, regular inspection or overhaul to check the coop- eration between the controller and the circuit breaker. After the completion of the test, display the mechanism action time or test state.
Use tips
1. This function can only be used during field deb1 ugging or maintenance of the circuit breaker, do not use it at will during normal operation;
2. Before each closing, the red reset button on the control panel must be pressed to close the circuit breaker again and put into operation;
Fault record and query function
When a fault trip occurs, the controller automatically records the fault current and operation time. You can press "Search" to query the fault record.
Self-diagnostic function
The self-diagnosis function of the controller is mainly used for the inspection and maintenance of its own operating status, and can detect the transformer signal breakage, magnetic flux breakage, circuit breaker rejection, and self-fault in realtime.
Indicator full display function
The controller can light up all the nixie tubes and indicators, this function is used to check whether all the light emitting devices are normal.
Real-time Clock (RTC) function (optional)
The controller provides the real-time clock function to display the current date and time and record the fault time when a fault occurs.
Voltmeter function (optional)
The controller can be equipped with voltmeter, voltmeter can display the current three-phase line voltage Uab, Ubc, Uca, phase voltage Uan, Ubn, Ucn,voltage frequency F in real time;
Temperature protection function (optional F)
Control can be optional circuit breaker bus temperature protection function, through the external temperature acquisition module of the compa- ny, each pole bus is installed with a temperature sensor, the module can collect 3 or 4 pole circuit breakers; The controller and the temperature acquisition module are connected by RS485, and the collected temperature is displayed on the controller. When the temperature is detected to reach the setting
Value initiates delay and trip action.
Temperature Start value =25 to 160 ° C +OFF. OFF indicates that the temperature protection function is disabled and the return difference is 5 ° C. Protection start delay =1~1800s+OFF,OFF indicates only alarm but no action.
(Usage instructions) : When the temperature alarm only does not trip, the alarm starting value = the set temperature starting value, the starting delay of 1s, the return difference is 5 °C ; Alarm Lcd backlight yellow, self-diagnosis display E-03; If the relay output is required, the relay can be set to 11.09 system selfdiagnosis fault;
Pressure recloser function (F type optional)
According to the Notice of the State Grid Corporation on the issuance of distributed power grid-connected opinions and Specifications, the
special switch should have the function of losing voltage opening and checking voltage closing, and the setting value of losing voltage opening should be adjusted to 20%UN, 10 seconds, and the setting value of detecting voltage should be adjusted to greater than 85%UN. According to the requirements of the code, the intelligent controller adds the function of "loss of pressure opening and detection of pressure closing" .
Loss of pressure opening function
When the minimum value of the three line voltages is less than the set value of the no-voltage start, after the set delay time, the switch control passive contact action, the output mode is 100ms pulse, and the window displays "U-F" .
If the failure of opening is caused by the abnormal control loop in the process of opening, "E-09" will be displayed in the self-detection informa- tion, and the opening pulse signal will not be output at this time.
After checking and eliminating the fault of the opening loop, press the reset key to recover
Pressure recloser function (F type optional)
According to the Notice of the State Grid Corporation on the issuance of distributed power grid-connected opinions and Specifications, the
special switch should have the function of losing voltage opening and checking voltage closing, and the setting value of losing voltage opening should be adjusted to 20%UN, 10 seconds, and the setting value of detecting voltage should be adjusted to greater than 85%UN. According to the requirements of the code, the intelligent controller adds the function of "loss of pressure opening and detection of pressure closing" .
Loss of pressure opening function
When the minimum value of the three line voltages is less than the set value of the no-voltage start, after the set delay time, the switch control passive contact action, the output mode is 100ms pulse, and the window displays "U-F" .
If the failure of opening is caused by the abnormal control loop in the process of opening, "E-09" will be displayed in the self-detection informa- tion, and the opening pulse signal will not be output at this time.
After checking and eliminating the fault of the opening loop, press the reset key to recover
Pressure loss switching function parameter table |
Parameter name |
Adjustment range |
Adjust step size |
Factory default |
Remark |
Protect startup settings |
60V~1200V |
1V |
80V |
80V=(20%×UN)=(20%×400V) |
Delay time set value |
0.2~60s |
0.1s |
3.0s |
|
Execution mode |
Switch off/switch off |
|
Off |
|
Output mode |
Switching relay 100ms pulse output |
en the minimum value of the three line voltages is less than the set value of the no-voltage start, after the setting delay time, the closing con- trol passive contact action, the output mode is 100ms pulse, and the window displays "U-H" .
If the closing failure is caused by the abnormal control loop during the closing process, "E-09" will be displayed in the self-detection information, and the closing pulse signal will not be output at this time. After checking and eliminating the fault of the closing loop, press the reset key to
recover.
Pressure closing function parameter table |
Parameter name |
Adjustment range |
Adjust step size |
Factory default |
Remark |
Protect startup settings |
60V~1200V |
1V |
340V |
340V=(85%×UN)=(85%×400V) |
Delay time set value |
0.2 ~ 60 s |
0.1s |
1.0s |
|
Execution mode |
Turn off/turnoff |
|
Close |
|
Output mode |
Closing relay 100ms pulse output |
Communication function
H-type controller can realize telemetry, remote control, remote adjustment, remote communication and other functions by MODBUS protocol
through communication port. The output of communication port adopts photoelectric isolation device, which is suitable for strong electrical inter- ference environment. For details of the communication, see Type H Communication Protocol.
Note: - Basic function: ○ - co-option function
Controller terminal definition |
Serial number |
Wire number |
Function description |
Remark |
1 |
1,2 |
Auxiliary power input |
M type factory default (serial number 1-5) H type factory default (serial number 1-11) |
2 |
3,4,5 |
Fault trip contact output (4# is the common end) |
3 |
6,7 |
Circuit breaker status auxiliary contact 1 Output |
4 |
8,9 |
Circuit breaker status auxiliary contact 2 output |
5 |
20 |
Protected area (PE) |
6 |
10,11 |
RS485 communication port leads terminals A and B |
7 |
12,13 |
Relay (D01) contact output |
8 |
14,15 |
Relay (D02) contact output |
9 |
16,17 |
Remote control tripping relay contact Output (D03) |
10 |
18,19 |
Remote closing relay contact output (D04) |
11 |
21,22,23,24 |
Voltage measurement input: N,A, B, C |
12 |
25,26 |
3P+N structure is connected to the neutral line transformer; Connect the leakage transformer ZCT1 for leakage protection |
Order specification |
Use tips
Q- undervoltage release device (can be connected to the "emergency stop" button when in use); X-closed electromagnet (normally closed aux- iliary contact can be connected in series when in use); SB2- manual switch button; F-shunt trip device (normally open auxiliary contact can be connected in series when in use);M- motor; SB1- Manual closing button;
Communication network
For details about the communication network of the controller, see the Communication Network Description of the Controller 3.
Precautions for operation and maintenance of the controller are as follows:
1. The controller shall be operated carefully according to the requirements of this Manual.
2. After assembling with the circuit breaker, the protective cover should be sealed during normal operation to prevent panel damage.
3. the normal operation should often check the controller system self-diagnosis information or alarm information, found problems should be ana- lyzed and processed in time.
4. Should regularly check the fastening of the connection parts, if loose should be tightened in time.
5. After the fault trip, the cause of the fault should be carefully analyzed, and the red mechanical reset button on the panel can be put into use again after the fault is removed.
Attachments
Leakage transformer
When the earth protection selects the leakage type, it is necessary to add the leakage transformer (ZCT), and its installation size is shown in the figure:
3P+N External neutral wire transformer installation size table (size unit mm) |
|
A |
B |
C |
D |
E |
F |
Box I transformer |
60 |
20 |
90 |
44 |
90 |
37 |
Box & transformer |
90 |
30 |
108 |
44 |
105 |
37 |
WK-200 temperature acquisition module is a newly developed module for circuit breaker temperature measurement and control. Its characteris- tics are as follows:
1. Can be used with the company's series of intelligent controller or independent use, to achieve temperature collection, overtemperature pro- tection or alarm output, data remote and other functions.
2. With the temperature sensor, the temperature of up to 4 busbars can be collected (with 3-pole or 4-pole switch).
3. Equipped with one RS485(using MODBUS protocol) interface, you can achieve data communication with the company's controller or other equipment.
4. This module can set temperature protection parameters independently, equipped with 1 relay output contact; According to user requirements can be used for over-temperature alarm/start cooling/overtemperature
5. switch and other functions.
Hint
1. N pole transformer only hollow transformer, no speed saturation transformer; The cable length between the controller and the controller is less than 10m.
2. If you have any other size requirements, please contact us.
Product parameter
1. Working power supply :AC220V or DC24V, ≤ 2W, error ±20%(instructions when ordering)
2. Input specif ications :1~4 temperature probes (instructions when or dering)
3. Relay capacity :AC250V/10A or DC30V/10A
4. Measuring range :0~200°C , error ±1%
5. Communication: one RS485 communication (support Modbus communication protocol)
6. Overall size :L102×W55×H45mm
Set parameters
item |
Set range |
Initial value |
remarks |
Temperature protection start value |
10°C ~160°C |
150°C |
If the current temperature is higher than the start value, control the output |
Temperature protection returned value |
9C~159C |
145°C |
If the current temperature is lower than the returned value, the output stops |
Correspondence address |
1~255 |
1 |
|
Communication baud rate |
/ |
9.6 k |
1.2k,2.4k,4.8k,9.6k,19.2k |
Operation instruction
1. Temperature query: The main screen displays the current maximum temperature of TA,TB,TC,TN. Press (up) or (Down) to switch the tem- perature of TA,TB,TC,TN.
2. Parameter modification: click (Setting) to enter parameter setting; If the digital tube is blinking and A is steady on, it indicates that the param- eters are being set.
Press (Up) or (Down) to modify the current parameter. Click (Settings) to save the current parameter and switch to the next parameter.
Tip: Click (Settings) when A,B,C,N cycle light,A represents the start value,B represents the return value,Crepresents the communication
address,N represents the communication baud rate); Click the (Manual/Cancel) key to cancel the current setting and exit the setting state.
3. Relay manual output: in the main interface, click (manual/cancel) key to switch manual/automatic relay output; Manual ,Output light is lit to manual output mode; (Manual) When the lamp is off,it is in automatic working mode, and the output is automatically controlled according to the temperature parameter set by the module. When there is (output), the lamp is on.
4. Temperature sensor disconnected detection: When a phase temperature sensor is disconnected or not connected, (--) is displayed when querying the phase temperature, please remove the exception in time.
Recommended size and quantity of external bronze plate |
Model number |
Maximum working current |
T:40°C Number of busbars |
T:50°C Number of busbars |
T:60°C Number of busbars |
5mm thickness |
10mm thickness |
5mm thickness |
10 mm thickness |
5mm thickness |
10mm thickness |
NV-800 |
800 |
2b.50×5 |
1b.50×10 |
2b.50×5 |
1b.50×10 |
2b.50×5 |
1b.50×10 |
NV-1000~1250 |
1000~1250 |
3b.50×5 |
1b.50×10 |
3b.50×5 |
2b.50×10 |
3b.50×5 |
2b.50×10 |
NV-1600 |
1600 |
3b.50×5 |
2b.40×10 |
3b.50×5 |
2b.50×10 |
4b.50×5 |
2b.50×10 |
"Break" locking device
The "off" lock device locks the off button of the circuit breaker in the pressed position, at which time the circuit breaker will not close.
After the user chooses the installation, the factory provides the lock and key; Three circuit breakers with three identical locks and two keys
Product Catalog
Company Profile
Our Advantages
Our Clients/Partners
Packaging & Shipping