CNC Ycb6n-32 in 6~32A 230V 4ka Low Voltage MCB Miniature Circuit Breaker
1.Overload protection
2.Short circuit protection
3.Controlling
4.Used in residential building, non-residential building, energy source industry and infrastructure.
5.According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln
Type Standard |
|
lEC/EN 60898-1 |
Electrical features |
Rated current ln |
A |
6, 10, 16, 20, 25, 32 |
Poles |
P |
1P+N |
Rated voltage Ue |
V |
230 |
Insulation voltage Ui |
V |
500 |
Rated frequency |
Hz |
50/60 |
Rated breaking capacity |
A |
3000 |
Rated impulse withstand voltage(1.2/50)Uimp |
V |
4000 |
Dielectric test voltage at ind. Freq. for 1min |
kV |
2 |
Pollution degree |
|
2 |
Thermo-magnetic release characteristic |
|
B, C |
Mechanical features |
Electrical life |
t |
4000 |
Mechanical life |
t |
10000 |
Protection degree |
|
IP20 |
Reference temperature for setting of thermal element |
ºC |
30 |
Ambient temperature (with daily average≤35ºC) |
ºC |
-5~+40 |
Storage temperature |
ºC |
-25~+70 |
Installation |
Terminal connection type |
|
Cable/Pin-type busbar |
Terminal size top / bottom for cable |
mm2 |
16 |
AWG |
18-5 |
Terminal size top / bottom for busbar |
mm2 |
10 |
AWG |
18-5 |
Tightening torque |
N*m |
2 |
In-Ibs |
18 |
Mounting |
|
On DIN rail EN 60715(35mm)by means of fast clip device |
Connection |
|
From top and bottom |